DRY TYPE TRANSFORMER

1. GENERAL
Transformer Type Three-phase, dry-type transformer, suitable for indoor installation
Applicable Standards IEC 60076 – Power Transformers
IEC 60076-11 – Dry-Type Transformers
IEC 60076-5 – Short-Circuit Withstand
IEC 60076-10 – Sound Level
2. ELECTRICAL RATINGS
Rated Power kVA ___
Primary Voltage kV ___
Secondary Voltage V ___
Frequency Hz 50
Connection Vector Group Dyn11 (typical) / Yyn0 / As specified
Cooling Method AN (Air Natural) / ANAF (Air Natural Air Forced)
Insulation Class Class F or Class H
Temperature Rise °C ≤ 100°C for Class F
≤ 125°C for Class H
3. PERFORMANCE
Efficiency As per IEC 60076-20 or local MEPS
Impedance Voltage % ___ (typical 4 – 6%)
Noise Level As per IEC 60076-10
Partial Discharge pC < 10
Short-Circuit Withstand Complies with IEC 60076-5
Cooling Fans (ANAF) Automatic, temperature-controlled
4. CONSTRUCTION
Core High-grade, grain-oriented CRGO silicon steel
Step-lap joint for reduced losses
Anti-corrosion coating
Windings – Option A (Cast Resin) LV and HV windings fully encapsulated in epoxy resin
High mechanical strength for short-circuit withstand
Conductors: Copper (standard) or Aluminium (if specified)
Windings – Option B (VPI Type) Copper windings vacuum pressure impregnated with epoxy varnish
Class F or H insulation
Conductors: Copper (standard) or Aluminium (if specified)
Enclosure IP21 / IP31 / IP41 / IP54
Ventilated steel enclosure with access doors
Color: RAL 7032 or RAL 7035
Base channels for forklift movement
5. STANDARD ACCESSORIES
Temperature Sensors PT100 for LV and HV windings
Temperature Controller Digital type with alarm relay, trip relay,
fan control (if equipped)
Terminal Boxes LV and HV terminal connection box
Earthing Earthing bar
Nameplate Stainless steel
Optional Accessories Surge arresters
Wheels
Anti-vibration pads
K-factor for nonlinear load applications
6. PROTECTION & SAFETY
Overtemperature Protection Alarm and trip
Overcurrent Protection Upstream circuit breaker
Touch Safety IP-rated
Mechanical Safety Enclosure with mechanical interlocks (if required)