MV VARIABLE FREQUENCY DRIVE (VFD)

MV VFD is a medium voltage motor speed control device using PWM (Pulse Width Modulation) or multilevel MVD technology to control motor speed, torque, and current efficiently, safely, and stably. The VFD must be suitable for MV motors of the Induction Motor or Synchronous Motor type.

No Section Parameter Unit Requirement
1 Applicable Standards Power Drive System-IEC 61800-2 / IEC 61800-4
Rotating Machine-IEC 60034
IP Protection-IEC 60529
Switchgear Assembly-IEC 61439
Semiconductor Converter-IEC 60146
Harmonic Limits-IEEE 519
Motor for VFD Application-NEMA MG-1 Part 31
Local Standard-SPLN / SNI (if required)
2 Input Power Rated Input VoltagekV3.3 / 6.6 / 11
FrequencyHz50/60 ± 5%
Voltage Tolerance%±10
Short Circuit RatingkA≥ 31.5
Power Factor-≥ 0.95 lagging
3 Motor Data Rated PowerkW___
Rated VoltagekV___
Rated CurrentA___
Speedrpm___
Duty-S1 Continuous
4 MV VFD Technology Inverter Topology-Multilevel
Acceptable Topology-CHB / NPC / ANPC
Not Allowed-Two-level topology
Output Waveform-Near sinusoidal
dv/dt-Low, motor-safe (IEC compliant)
Input Harmonics-IEEE 519 compliant
5 Performance Output Frequency RangeHz0–60 (option up to 75)
Frequency AccuracyHz±0.01
Voltage Control-V/f proportional
Efficiency%≥ 96 at rated load
Overload Capacity-150% / 60 s, 180% / 10 s
Input THDi%≤ 5
Output THDv%≤ 5
6 Construction Enclosure Type-Metal enclosed
IP Rating (Indoor)-IP42
IP Rating (Outdoor)-IP54
Arc Resistant-Optional
Cooling System-Air-cooled, forced ventilation
Temperature Monitoring-Cell, transformer, enclosure
7 Control & Protection Control Mode-V/f, Sensorless Vector (optional)
PID Controller-Built-in
Flying Start-Available
Protection Functions-OC, SC, OV/UV, GF, OL, Stall, OT, Cooling Fail
8 HMI & Communication Display-LCD / 7–10” Touchscreen
Monitoring & Logging-Real-time, ≥1000 events
Communication Protocol-Modbus RTU/TCP, Profibus, Profinet, Ethernet/IP, OPC-UA
9 Input Transformer Type-Multi-winding phase shifting
Cooling-ONAN / ONAF
Insulation Class-F / H
10 Harmonic Mitigation Pulse Configuration-12 / 18 / 24 pulse
Harmonic Filter-Passive / Active (optional)
Compliance-IEEE 519-2022