General
This specification defines the minimum technical requirements for the engineering, design, materials, manufacturing, assembly, wiring, factory testing, inspection, delivery, and documentation of Protection & Control Relay Panels for Medium-Voltage (MV) and High-Voltage (HV) substations.
The panel can provide devices as client requirement:
- Protection relays
- Control and status devices
- Metering instruments
- Auxiliary relays
- Communication modules
- Annunciator and alarm devices
- Wiring, terminals, and accessories
The Protection relay can provide many type as client requirement:
- Transformer Protection
- Feeder Protection
- Busbar Protection
- Line / Incoming Protection
- Generator / Motor Protection
- Others
Applicable Standards
All equipment shall comply with the latest editions of :
IEC Standards
- IEC 60255 – Measuring relays and protection equipment
- IEC 61850 – Substation automation & communication
- IEC 61439 / IEC 62271 – LV & MV switchgear assemblies
- IEC 60529 – IP degree of protection
- IEC 60044 / IEC 61869 – Instrument transformers
- IEC 61000 – EMC Electromagnetic compatibility
- IEC 60947 – Controlgear and switching devices
- IEC 60364 – Electrical installations
IEEE/ANSI Standards (optional based on project)
- IEEE C37 series
- IEEE 242 (Buff Book)
- IEEE 1584 (Arc Flash)
Local Regulations
- Local utility requirements (PLN, TNB, etc.) where applicable
- Local safety and electrical codes
Environmental Conditions
Panels shall be designed for:
- Ambient temperature: –5°C to +50°C (or as specified)
- Relative humidity: up to 95% non-condensing
- Installation altitude: ≤ 1000 m
- Seismic rating: IEC 60068-3-3 or equivalent
- Indoor or outdoor use as defined in datasheet
Construction Requirements
- Enclosure
- Material: Steel Plate or client requested
- Sheet thickness:
- 2 mm (body)
- 3 mm (doors/base frame)
- or client requested
- Modular design, bolted frame
- Powder coating: RAL 7035 (80–120μm thickness) or client requested
- Rear access via hinged door
- Cable entry: bottom (default) or top (optional)
- Degree of Protection
- Indoor panels: minimum IP4X
- Outdoor panels: minimum IP54, with canopy
- or client requested